16 December 2022 Failure analysis on ball head hanging ring of suspension insulator used in 110kV transmission line
Xin Qiao, Hao Chen, Yuhong Gu, Yunfei Sun, Zhihao Zhang
Author Affiliations +
Proceedings Volume 12500, Fifth International Conference on Mechatronics and Computer Technology Engineering (MCTE 2022); 1250014 (2022) https://doi.org/10.1117/12.2660411
Event: 5th International Conference on Mechatronics and Computer Technology Engineering (MCTE 2022), 2022, Chongqing, China
Abstract
The worn ball head hanging ring used in suspension insulator of 110kV transmission line was investigated by means of microstructure analysis, Macro-morphology inspection, fracture morphology analysis and hardness test. The results show that the material of the ball head hanging ring with low hardness and poor wear resistance and the galloping of the conductor were the main reason for its severe wear. Additionally, effective suggestions were put forward in order to improve the wear resistance of the ball head hanging ring in order to ensure the safety and stability of the power grid.
© (2022) COPYRIGHT Society of Photo-Optical Instrumentation Engineers (SPIE). Downloading of the abstract is permitted for personal use only.
Xin Qiao, Hao Chen, Yuhong Gu, Yunfei Sun, and Zhihao Zhang "Failure analysis on ball head hanging ring of suspension insulator used in 110kV transmission line", Proc. SPIE 12500, Fifth International Conference on Mechatronics and Computer Technology Engineering (MCTE 2022), 1250014 (16 December 2022); https://doi.org/10.1117/12.2660411
Advertisement
Advertisement
RIGHTS & PERMISSIONS
Get copyright permission  Get copyright permission on Copyright Marketplace
KEYWORDS
Head

Resistance

Failure analysis

Inspection

Iron

Scanning electron microscopy

Manufacturing

Back to Top