Abstract
Breaking capacity of vacuum circuit breakers is limited by dynamic voltage withstanding of their vacuum interrupters in a sense. Dynamic insulation in a vacuum interrupter can be represented externally by their dielectric recovery behavior and the stability of voltage withstanding. The internal feature of dynamic insulation includes two sides: one is the weak points under high electric stress, the other is macro-particles produced in the process of breaking high current. Some experiments were made to investigate these features. After analysis of the results, we given some measures to improve dynamic insulation of vacuum interrupters.