2 July 2007 New optical hydrogen sensor with fast response time based on multilayer palladium-nickel-PTFE thin film for explosion-proof detection of high H2 concentrations of 1-100%
Author Affiliations +
Proceedings Volume 6619, Third European Workshop on Optical Fibre Sensors; 66191L (2007) https://doi.org/10.1117/12.738422
Event: Third European Workshop on Optical Fibre Sensors, 2007, Napoli, Italy
Abstract
Hydrogen detection is of great interest in many fields such as hydrogen concentrations around the explosive limit of 4% or in areas where strong electrical fields are present. Optical sensors have the advantage that they are not affected by these conditions. A comparison of three thin film sensors made of Pd, Pd Ni and Pd Ni / PTFE to detect H2 is made. The double-sided samples are purpose built by plasma sputtering, with a thickness of 4nm on each side. It is shown that the signal of a pure Pd deposit is strong but it cannot resist higher H2 concentrations. The Pd Ni deposit has shown good results and is able to resolve even higher concentrations of 10% H2 but cannot resist high concentrations of H2 over many cycles. The new Pd Ni / PTFE deposit can be used many times for concentrations up to 100% without any damage and can detect concentrations of 1-100% of H2. Furthermore the response time for deposits of different thickness is tested.
© (2007) COPYRIGHT Society of Photo-Optical Instrumentation Engineers (SPIE). Downloading of the abstract is permitted for personal use only.
Gero Bramann, Gero Bramann, Bernd Zacharias, Bernd Zacharias, Marion Wienecke, Marion Wienecke, } "New optical hydrogen sensor with fast response time based on multilayer palladium-nickel-PTFE thin film for explosion-proof detection of high H2 concentrations of 1-100%", Proc. SPIE 6619, Third European Workshop on Optical Fibre Sensors, 66191L (2 July 2007); doi: 10.1117/12.738422; https://doi.org/10.1117/12.738422
PROCEEDINGS
4 PAGES


SHARE
RELATED CONTENT


Back to Top