Paper
22 July 2016 CARMENES-NIR channel spectrograph cooling system AIV: thermo-mechanical performance of the instrument
S. Becerril, E. Mirabet, J. L. Lizon, M. Abril, C. Cárdenas, I. Ferro, R. Morales, D. Pérez, A. Ramón, M. A. Sánchez-Carrasco, A. Quirrenbach, P. Amado, I. Ribas, A. Reiners, J. A. Caballero, W. Seifert, J. Herranz
Author Affiliations +
Abstract
CARMENES is the new high-resolution high-stability spectrograph built for the 3.5m telescope at the Calar Alto Observatory (CAHA, Almería, Spain) by a consortium formed by German and Spanish institutions. This instrument is composed by two separated spectrographs: VIS channel (550-1050 nm) and NIR channel (950- 1700 nm). The NIR-channel spectrograph's responsible is the Instituto de Astrofísica de Andalucía (IAACSIC). It has been manufactured, assembled, integrated and verified in the last two years, delivered in fall 2015 and commissioned in December 2015.

One of the most challenging systems in this cryogenic channel involves the Cooling System. Due to the highly demanding requirements applicable in terms of stability, this system arises as one of the core systems to provide outstanding stability to the channel. Really at the edge of the state-of-the-art, the Cooling System is able to provide to the cold mass (~1 Ton) better thermal stability than few hundredths of degree within 24 hours (goal: 0.01K/day).

The present paper describes the Assembly, Integration and Verification phase (AIV) of the CARMENES-NIR channel Cooling System implemented at IAA-CSIC and later installation at CAHA 3.5m Telescope, thus the most relevant highlights being shown in terms of thermal performance.

The CARMENES NIR-channel Cooling System has been implemented by the IAA-CSIC through very fruitful collaboration and involvement of the ESO (European Southern Observatory) cryo-vacuum department with Jean-Louis Lizon as its head and main collaborator. The present work sets an important trend in terms of cryogenic systems for future E-ELT (European Extremely Large Telescope) large-dimensioned instrumentation in astrophysics.
© (2016) COPYRIGHT Society of Photo-Optical Instrumentation Engineers (SPIE). Downloading of the abstract is permitted for personal use only.
S. Becerril, E. Mirabet, J. L. Lizon, M. Abril, C. Cárdenas, I. Ferro, R. Morales, D. Pérez, A. Ramón, M. A. Sánchez-Carrasco, A. Quirrenbach, P. Amado, I. Ribas, A. Reiners, J. A. Caballero, W. Seifert, and J. Herranz "CARMENES-NIR channel spectrograph cooling system AIV: thermo-mechanical performance of the instrument", Proc. SPIE 9912, Advances in Optical and Mechanical Technologies for Telescopes and Instrumentation II, 991262 (22 July 2016); https://doi.org/10.1117/12.2232322
Lens.org Logo
CITATIONS
Cited by 2 scholarly publications.
Advertisement
Advertisement
RIGHTS & PERMISSIONS
Get copyright permission  Get copyright permission on Copyright Marketplace
KEYWORDS
Cooling systems

Near infrared

Sensors

Spectrographs

Cryogenics

Observatories

Telescopes

RELATED CONTENT

Detector quality control
Proceedings of SPIE (December 13 2020)
The ESO VLT X shooter instrument software in the VLT...
Proceedings of SPIE (June 27 2006)
Optical design of a red-sensitive spectrograph
Proceedings of SPIE (September 24 2012)
PRAXIS a low background NIR spectrograph for fibre Bragg...
Proceedings of SPIE (September 13 2012)

Back to Top